
Technical Manual : 6521355 V1.8.0 07/2014
Design Features & Information
MINIMUM SYSTEM WATER VOLUME CALCULATIONS
(DX Mechanical Cooling Mode Requirements)
System fluid 20% ethylene glycol / 80% water.
Where the system permanent heat load is known and the preferred method:
Minimum Compressor
Run Time (min)
Chiller Loading Factor
(1)
Output = (kW) Cooling Duty, Output kW, refer to Performance Data, on page 20
SHC = (kJ/kg°C) Specific Heat Capacity, 3.9 based on 20% ethylene glycol concentration.
ΔT = (°C) Difference of Entering Water and Leaving Water temperature
MC% = Minimum Capacity expressed as a % of Output, refer to Mechanical Data, on
page 29
PHL = (kW) Customer Permanent Heat Load
Model Ref. = LCC40
Ambient: = 35°C
Fluid = 20% Ethylene Glycol
Inlet Fluid Temp. = 7°C
Outlet Fluid Temp. = 12°C (5°C
T)
Customer Permanent Head Load = 20.0 kW
Output at given conditions = 33.7 kW
Where the system permanent heat load is unknown:
Minimum Compressor
Run Time (min)
Model Ref. = LCC40
Ambient: = 35°C
Fluid = 20% Ethylene Glycol
Inlet Fluid Temp. = 7°C
Outlet Fluid Temp. = 12°C (5°C
T)
Output at given conditions = 33.7 kW
Komentarze do niniejszej Instrukcji