Performance Data
For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.
All free-cooling units should use a MINIMUM 20% glycol concentration.
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
Model Ref. = LCC40
Ambient: = 35°C
Fluid = 30% Ethylene Glycol
Inlet Fluid Temp. = 7°C
Outlet Fluid Temp. = 12°C (5°C
T)
Plot from curve (refer to Waterside
Pressure Drop (kPa), on page 24)
Output = (kW) Output kW, refer to Capacity Data - DX (Mechanical) Cooling, on page 20
Input = (kW) Input kW, refer to Capacity Data - DX (Mechanical) Cooling, on page 20
ΔT = (°C) Difference of Entering Water and Leaving Water temperature
All performance data is supplied in accordance with BS EN 14511-1:2013